Implementing VLF as diagnostic test for HV motors and generators : A comparative study of diagnostic tests performed at different frequencies

High voltage testing of the stator winding insulation is one of the most recognized methods used to determine the state of degradation in the insulation. HV tests performed at 0.1 Hz do have potential advantages compared to more traditional 50 Hz tests. This thesis therefore aims to perform and compare tan delta, capacitance and partial discharge measurements on stator windings when using a 0.1 Hz voltage source and a more traditional 50 Hz voltage supply. Several associated test parameters with considerable influence on the test results were varied during the tests. An associated data analysis followed that was focused on the differences and similarities of the analyzed parameters and the results due to the differences in frequency. The results show that there are substantial levels of noise present in the partial discharge measurements when utilizing the VLF voltage source. There are also more numerous partial discharges for VLF measurements than for regular power frequency measurements if the same amount of voltage cycles is considered. The generated patterns show similarities with those generated at 50 Hz, but a larger sample base is probably needed for more thorough conclusions. The tan delta/capacitance part of the test do indicate potential advantages compared to power frequency measurements regarding the sensitivity in the measurements.

Identiferoai:union.ndltd.org:UPSALLA1/oai:DiVA.org:uu-393813
Date January 2019
CreatorsHedlund, Niklas
PublisherUppsala universitet, Institutionen för teknikvetenskaper
Source SetsDiVA Archive at Upsalla University
LanguageEnglish
Detected LanguageEnglish
TypeStudent thesis, info:eu-repo/semantics/bachelorThesis, text
Formatapplication/pdf
Rightsinfo:eu-repo/semantics/openAccess
RelationUPTEC ES, 1650-8300 ; 19025

Page generated in 0.0025 seconds