Back to search

Georgia Institute of Technology

Control of data center cooling using data driven heuristic approach

Abstract

dc:description.abstract

This thesis proposes a method of heuristic temperature prediction with real-time data to control the cooling infrastructure of a data center. This thesis addresses thermal management in data centers through the control scheme in one case study, in which dynamic control of the air conditioner temperature set point with heuristic temperature prediction of the server rack inlet temperature results in reaching a target server rack temperature in ~30 min. This thesis addresses energy savings through another case study, in which dynamic controls utilize outside air economization, resulting in energy reduction of ~1-2 kW while reducing space temperature variation to under 2°C during normal operation.

Degree

thesis:*
Level thesis:degree_level
Masters
Department dc:contributor.department
Mechanical Engineering
Grantor dc:publisher
Georgia Institute of Technology
Year dc:date.issued
2019

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Baxendale, Mitchell David
Advisor dc:contributor.advisor
  • Joshi, Yogendra
Committee members dc:contributor.committeemember
  • Yoda, Minami
  • Loutzenhiser, Peter

Subjects

dc:subject × 11

Rights

Language dc:language.iso
en_US

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1853/61724

Chain of custody

source
Harvested from
Georgia Tech
Base URL
repository.gatech.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
citation

Baxendale, Mitchell David. Control of data center cooling using data driven heuristic approach. Masters thesis, Georgia Institute of Technology, 2019. http://hdl.handle.net/1853/61724