Digital Repository at the University of Maryland
Experimental and Computational Analysis of the Fire Suppression Effectiveness of Halon 1301 Replacements
Abstract
dc:description.abstractExperimental and computational work was performed to help understand why sub-inerting concentrations of HFC-125 (C2HF5) produced overpressures in the FAA aerosol can explosion test. The fire suppression performance of HCFC-123 (C2HCl2F3) was also investigated to determine whether it may perform better than HFC-125. Thermodynamic analysis shows that both agents increase the overall heat release for lean mixtures containing the aerosol can contents. HFC-125 also increases the overall reaction rate when added to lean mixtures. The overall reaction rate of mixtures containing HCFC-123 is generally lowered when sub-inerting concentrations are added. Experimental results showed that HCFC-123 has a lower minimum inerting concentration (8.9%) than HFC-125 (13.5%). Mixtures containing HCFC-123 were found to produce peak pressures in the 2 L chamber that were estimated to cause overpressures in the FAA chamber. Nitrogen dilution resulting in 20% oxygen in air was successful at eliminating the overpressure of mixtures containing HCFC-123.
Degree
thesis:*- Department dc:contributor.department
- Fire Protection Engineering
- Grantor dc:publisher
- Digital Repository at the University of Maryland
- Year dc:date.issued
- 2012
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Pagliaro, John Leonard
- Advisor dc:contributor.advisor
-
- Sunderland, Peter B
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/1903/13653