Reducing stator current harmonics for a doubly-fed induction generator connected to a distorted grid

Abstract

dc:description.abstract

The Department of Defense (DoD) is increasing its demand for reliable renewable energy sources. The doubly-fed induction generator (DFIG) is widely used to extract electrical energy from wind and is a useful means for the DoD to achieve its renewable energy goals. The DFIG is susceptible to electric grid voltage harmonics, which is a potential obstacle for implementing stable wind-energy systems. Two existing rotor voltage controllers are modeled in this thesis for eventual implementation in a laboratory DFIG wind energy system. The first controller uses multiple proportional-integral (PI) controllers to filter out the fifth and seventh stator current harmonics. Each PI controller operates in a reference frame that rotates in synchronicity with the harmonic that is being filtered. The second controller operates in the synchronous reference frame and simultaneously filters both the fifth and seventh stator current harmonics using a double integrator called a proportional-resonant controller (PR). The PI controller is shown to be more effective at eliminating the stator current than the PR controller but has a slower reaction time. The PR controller requires fewer computations but has more stability concerns. Both controllers reduce torque oscillations resulting from the grid distortion by approximately the same amount.

Degree

thesis:*
Name thesis:degree_name
Master of Science in Electrical Engineering
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Electrical Engineering
Department dc:contributor.department
Electrical and Computer Engineering (ECE)
Grantor dc:publisher
Monterey, CA; Naval Postgraduate School
Year dc:date.issued
2013

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Pierce, Seth J.
Advisor dc:contributor.advisor
  • Julian, Alexander L.
Committee member dc:contributor.committeemember
  • Cristi, Roberto

Rights

dc:rights
Statement dc:rights
  • This publication is a work of the U.S. Government as defined in Title 17, United States Code, Section 101. Copyright protection is not available for this work in the United States.
  • Approved for public release; distribution is unlimited.

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/10945/37693

Chain of custody

source
Harvested from
Naval Postgraduate School
Base URL
calhoun.nps.edu/server/oai/request
Last updated
2026-11-19
Source record
OAI-PMH GetRecord
related terms
citation

Pierce, Seth J.. Reducing stator current harmonics for a doubly-fed induction generator connected to a distorted grid. Masters thesis, Monterey, CA; Naval Postgraduate School, 2013. https://hdl.handle.net/10945/37693