1 |
The evaluation of a solar-driven aqua-ammonia diffusion absorption heating and cooling cycle / M.C. Potgieter.Potgieter, Marthinus Christiaan January 2013 (has links)
Several steps are followed in order to evaluate the cycle as the title suggests. The diffusion absorption refrigerator (DAR) cycle performance is evaluated when using helium or hydrogen as auxiliary gas. A slight increase in COP is found when using helium, but it is not sufficient to justify the cost. A secondary simulation of an alternate dual-pressure cycle using a pump is done as feasibility comparison with the same parameters as the diffusion cycle. It was found that the second cycle is not acceptable due to high evaporator temperatures needed to ensure liquid enters the pump instead of partially evaporated solution. This would greatly increase the work input required for what essentially becomes a compressor.
Optimisation of the DAR is evaluated by simulating the use of a rectification column and the effects of different design points on overall performance. Meteorological data for Potchefstroom, South Africa is used to perform a yearly analysis on the simulated cycle and to specify a suitable design point. The use of a radiative cooling system as heat sink for the system is then investigated and incorporated into the system model.
Finally, the performance characteristics of the simulated DAR cycle are discussed, verified and compared with available data from similar research. It is shown that a 40% solution aqua-ammonia-hydrogen cycle driven by 526 kW of solar thermal energy at 130°C and a system pressure of 1.5 MPa can easily achieve a COP over 0.4 with an air-cooled absorber at 40°C and a water-cooled condenser at 35°C. A 231 kW refrigeration capacity at an average evaporator temperature of –20°C is achieved, satisfying the requirements for a domestic refrigeration system. / Thesis (MIng (Mechanical Engineering))--North-West University, Potchefstroom Campus, 2013.
|
2 |
The evaluation of a solar-driven aqua-ammonia diffusion absorption heating and cooling cycle / M.C. Potgieter.Potgieter, Marthinus Christiaan January 2013 (has links)
Several steps are followed in order to evaluate the cycle as the title suggests. The diffusion absorption refrigerator (DAR) cycle performance is evaluated when using helium or hydrogen as auxiliary gas. A slight increase in COP is found when using helium, but it is not sufficient to justify the cost. A secondary simulation of an alternate dual-pressure cycle using a pump is done as feasibility comparison with the same parameters as the diffusion cycle. It was found that the second cycle is not acceptable due to high evaporator temperatures needed to ensure liquid enters the pump instead of partially evaporated solution. This would greatly increase the work input required for what essentially becomes a compressor.
Optimisation of the DAR is evaluated by simulating the use of a rectification column and the effects of different design points on overall performance. Meteorological data for Potchefstroom, South Africa is used to perform a yearly analysis on the simulated cycle and to specify a suitable design point. The use of a radiative cooling system as heat sink for the system is then investigated and incorporated into the system model.
Finally, the performance characteristics of the simulated DAR cycle are discussed, verified and compared with available data from similar research. It is shown that a 40% solution aqua-ammonia-hydrogen cycle driven by 526 kW of solar thermal energy at 130°C and a system pressure of 1.5 MPa can easily achieve a COP over 0.4 with an air-cooled absorber at 40°C and a water-cooled condenser at 35°C. A 231 kW refrigeration capacity at an average evaporator temperature of –20°C is achieved, satisfying the requirements for a domestic refrigeration system. / Thesis (MIng (Mechanical Engineering))--North-West University, Potchefstroom Campus, 2013.
|
Page generated in 0.1166 seconds