Estudo e desenvolvimento de um microinversor empregando o conversor ?uk para microgera??o fotovoltaica

Cabral, Henrique Gabriel 29 August 2016 (has links)
Submitted by PPG Engenharia El?trica (engenharia.pg.eletrica@pucrs.br) on 2018-01-16T12:25:22Z No. of bitstreams: 1 Dissertacao Henrique Cabral Final.pdf: 7113504 bytes, checksum: 991064508825d35b392d6e41b5e9023f (MD5) / Approved for entry into archive by Caroline Xavier (caroline.xavier@pucrs.br) on 2018-01-26T13:01:29Z (GMT) No. of bitstreams: 1 Dissertacao Henrique Cabral Final.pdf: 7113504 bytes, checksum: 991064508825d35b392d6e41b5e9023f (MD5) / Made available in DSpace on 2018-01-26T13:06:39Z (GMT). No. of bitstreams: 1 Dissertacao Henrique Cabral Final.pdf: 7113504 bytes, checksum: 991064508825d35b392d6e41b5e9023f (MD5) Previous issue date: 2016-08-29 / This work presents a study and a development of a current source microinverter, based on the ?uk converter operating in discontinuous conduction mode, for microgeneration purposes based on photovoltaic systems. In this sense, we carried out a steady-state analysis of the ?uk converter, in order to establish the design criteria for the ?uk microinverter. All peripheral systems required for the microinverter operation have also been developed, and are included in this study, namely: the MPPT, PLL, and islanding detection algorithms. All control systems, i.e., the MPPT, PLL, and anti-islanding detection algorithms, were implemented in the DS1104 R&D controller board, from dSPACE?, using MATLAB/Simulink? to program it. / Este trabalho apresenta o estudo e o desenvolvimento de um microinversor de corrente, baseado no conversor ?uk, operando no modo de condu??o descont?nua, para a aplica??o em microgera??o fotovoltaica. Inicialmente, s?o desenvolvidos estudos de car?ter qualitativo e quantitativo do comportamento do microinversor de corrente baseado no conversor ?uk, os quais culminaram no desenvolvimento de crit?rios para o dimensionamento do conversor ?uk, que desempenha um papel central na estrutura do microinversor proposto. Sistemas perif?ricos necess?rios para a opera??o do microinversor, assim como aqueles exigidos pelas concession?rias de energia el?trica para a aplica??o em sistemas de microgera??o s?o estudados e desenvolvidos nessa disserta??o. Para tanto, a implementa??o de todos os sistemas de controle, ou seja, os algoritmos de MPPT, de sincronismo, e de detec??o da opera??o ilhada, foram realizados em ambiente MATLAB/Simulink? associada ? uma placa de desenvolvimento do fabricante alem?o dSPACE?, modelo DS1104, a qual permite o controle em tempo real dos transistores do microinversor.
2

Detecção de ilhamento de geradores síncronos distribuídos por correlações da mineração complexa de dados / Islanding detection of distributed synchronous generators by complex data-mining correlations

Gomes, Eduardo Augusto Pereira 31 August 2016 (has links)
Um dos principais problemas que podem ocorrer em sistemas de distribuição ou de subtransmissão de energia elétrica com geração distribuída (GD) é o ilhamento. O ilhamento ocorre quando um ou mais geradores distribuídos alimentam uma porção do sistema que se encontra eletricamente isolada do restante do sistema elétrico. Logo, geradores distribuídos têm de ser equipados com esquema de proteção anti-ilhamento, pois a operação ilhada pode colocar em risco a segurança das pessoas e equipamentos e pode deteriorar a qualidade da energia elétrica suprida aos consumidores locais. Este trabalho está inserido no contexto de proteção de sistemas elétricos de distribuição com GD e propõe uma nova técnica passiva-inteligente de proteção anti-ilhamento para geradores síncronos distribuídos. O método proposto utiliza a mineração de dados do Data Mining of Code Repositories (DAMICORE), o qual possui grandes potencialidades para descobrir correlações em dados complexos. Para realizar essa tarefa, três algoritmos são executados em sequência. São eles: o Normalized Compression Distance (NCD) para calcular a matriz de distância do conjunto de dados; o Neighbor-Joining (NJ) para construir as árvores filogenéticas; e por fim o Fast Newman (FN) para buscar grupos na árvore filogenética nos quais os dados apresentam alto grau de independência. O método de detecção de ilhamento nesta dissertação utiliza 10 características importantes dos sinais de tensão e corrente trifásicas no ponto de acoplamento comum (PAC). Essas 10 características são utilizadas como entrada ao DAMICORE para formular um algoritmo baseado em mineração de dados capaz de detectar ilhamento e de diferenciá-los de outros tipos de distúrbios. Os resultados mostram que o método identifica o ilhamento corretamente, detectando-o rapidamente, especialmente nos casos em que a detecção do ilhamento por relés baseados em medidas de frequência falha ou é lenta. / One of the main issues that can occur into distribution power systems with distributed generation is islanding. Islanding occurs when one or more distributed generators feed a portion of the distribution system that becomes electrically isolated from the rest of the power system. Thus, distributed generators have to be equipped with anti-islanding protection schemes, because the islanded operation may put at risk the safety of people and the equipment. It can also deteriorate the power quality supplied to local consumers. This work is in the context of the protection schemes for distribution power systems with distributed generation and it proposes a new intelligent passive anti-islanding protection scheme for distributed synchronous generators. The scheme is based on the Data Mining of Code Repositories (DAMICORE), which finds the similarity within complex data sets. This task is performed by computing the following algorithms, in sequence: the Normalized Compression Distance (NCD) to calculate a distance matrix among the data sets; the Neighbor-Joining (NJ) to build the phylogenetic trees; and the Fast Newman (FN) to find clusters with high degree of independence by using the phylogenetic trees. The proposed method comprises the extraction of 10 important features of the three-phase voltages and currents measured at the point of common coupling of the distributed generator. These 10 features are then used as input to the DAMICORE in order to formulate a data mining-based algorithm capable of detecting islanding and of distinguishing it from other disturbances. The results show that the method identifies the islanding correctly, detecting it quickly, especially where the detection of islanding by frequency-based relays are slow.
3

Detecção de ilhamento de geradores síncronos distribuídos por correlações da mineração complexa de dados / Islanding detection of distributed synchronous generators by complex data-mining correlations

Eduardo Augusto Pereira Gomes 31 August 2016 (has links)
Um dos principais problemas que podem ocorrer em sistemas de distribuição ou de subtransmissão de energia elétrica com geração distribuída (GD) é o ilhamento. O ilhamento ocorre quando um ou mais geradores distribuídos alimentam uma porção do sistema que se encontra eletricamente isolada do restante do sistema elétrico. Logo, geradores distribuídos têm de ser equipados com esquema de proteção anti-ilhamento, pois a operação ilhada pode colocar em risco a segurança das pessoas e equipamentos e pode deteriorar a qualidade da energia elétrica suprida aos consumidores locais. Este trabalho está inserido no contexto de proteção de sistemas elétricos de distribuição com GD e propõe uma nova técnica passiva-inteligente de proteção anti-ilhamento para geradores síncronos distribuídos. O método proposto utiliza a mineração de dados do Data Mining of Code Repositories (DAMICORE), o qual possui grandes potencialidades para descobrir correlações em dados complexos. Para realizar essa tarefa, três algoritmos são executados em sequência. São eles: o Normalized Compression Distance (NCD) para calcular a matriz de distância do conjunto de dados; o Neighbor-Joining (NJ) para construir as árvores filogenéticas; e por fim o Fast Newman (FN) para buscar grupos na árvore filogenética nos quais os dados apresentam alto grau de independência. O método de detecção de ilhamento nesta dissertação utiliza 10 características importantes dos sinais de tensão e corrente trifásicas no ponto de acoplamento comum (PAC). Essas 10 características são utilizadas como entrada ao DAMICORE para formular um algoritmo baseado em mineração de dados capaz de detectar ilhamento e de diferenciá-los de outros tipos de distúrbios. Os resultados mostram que o método identifica o ilhamento corretamente, detectando-o rapidamente, especialmente nos casos em que a detecção do ilhamento por relés baseados em medidas de frequência falha ou é lenta. / One of the main issues that can occur into distribution power systems with distributed generation is islanding. Islanding occurs when one or more distributed generators feed a portion of the distribution system that becomes electrically isolated from the rest of the power system. Thus, distributed generators have to be equipped with anti-islanding protection schemes, because the islanded operation may put at risk the safety of people and the equipment. It can also deteriorate the power quality supplied to local consumers. This work is in the context of the protection schemes for distribution power systems with distributed generation and it proposes a new intelligent passive anti-islanding protection scheme for distributed synchronous generators. The scheme is based on the Data Mining of Code Repositories (DAMICORE), which finds the similarity within complex data sets. This task is performed by computing the following algorithms, in sequence: the Normalized Compression Distance (NCD) to calculate a distance matrix among the data sets; the Neighbor-Joining (NJ) to build the phylogenetic trees; and the Fast Newman (FN) to find clusters with high degree of independence by using the phylogenetic trees. The proposed method comprises the extraction of 10 important features of the three-phase voltages and currents measured at the point of common coupling of the distributed generator. These 10 features are then used as input to the DAMICORE in order to formulate a data mining-based algorithm capable of detecting islanding and of distinguishing it from other disturbances. The results show that the method identifies the islanding correctly, detecting it quickly, especially where the detection of islanding by frequency-based relays are slow.
4

Metodologias de ajuste das proteções anti-ilhamento de geradores distribuídos considerando múltiplos eventos / Methodology to adjust distributed generation anti-islanding protections based on multiple events

Motter, Daniel 16 November 2017 (has links)
Os geradores distribuídos em sistemas de distribuição de energia elétrica devem ser desconectados em eventos de ilhamento, que ocorrem quando parte da rede elétrica torna-se eletricamente isolada da concessionária e o subsistema isolado continua a ser energizado pela geração distribuída. A proteção anti-ilhamento deve detectar tal condição operativa, porém pode não atuar em condições de pequenos desbalanços entre carga e geração, ou atuar incorretamente para eventos de outra natureza. Assim, um ajuste adequado dessa proteção deve desconectar o gerador rapidamente quando detecta o ilhamento e, simultaneamente, deve ser imune a eventos como curtos-circuitos e chaveamentos de carga, por exemplo. Esta pode ser uma tarefa muito difícil face às variações de carga e diferentes eventos de não ilhamento que podem ocorrer no sistema de distribuição. Portanto, nesta tese são propostas metodologias de ajuste das funções de proteção anti-ilhamento de sub/sobrefrequência, taxa de variação de frequência, salto de vetor e sub/sobretensão, que são técnicas convencionalmente utilizadas para a detecção de ilhamento de geração distribuída. O objetivo das metodologias é maximizar a detecção de ilhamento e minimizar a atuação incorreta, e são considerados cenários com múltiplos geradores distribuídos de diferentes tecnologias. Inicialmente, são explorados os principais fatores que afetam as proteções, tais como distribuição das cargas, fator de potência e desequilíbrio das cargas. Esta análise permite identificar os casos mais difíceis de detecção de ilhamento. Como segunda contribuição, foi proposta a metodologia de análise gráfica denominada Mapa de Ajustes, cuja eficácia foi comprovada por meio de casos de teste, mostrando ser capaz de melhorar a sensibilidade da proteção anti-ilhamento e minimizar atuação incorreta. Na sequência, é apresentado um método automático para ajuste e bloqueio de tensão e outro baseado em proteção adaptativa para ajuste das funções de proteção. Ambos são baseados na metodologia de mapa de ajustes. Os resultados indicam que é possível melhorar a detecção de ilhamento e diminuir a atuação incorreta quando utilizadas as metodologias propostas. / Distributed generators in power distribution systems must be disconnected after an islanding event, which occurs when part of the power grid becomes electrically isolated from the utility and the isolated subsystem continues to be energized by the distributed generation. The antiislanding protection has to detect such operating condition, which may fail for critical loading conditions, or operate incorrectly for events of other nature than islanding. Therefore, an appropriate protection setting should quickly disconnect the generator when an islanding event is detected, and simultaneously, must be immune to events such as short circuits and load switches. This can be a very difficult task due to load variations and different nonislanding events that may occur in the distribution system. Therefore, in this thesis is proposed methodologies to adjust the anti-islanding protection functions of under/overfrequency, rate of change of frequency, vector surge and under/overvoltage, which are techniques conventionally used for islanding detection of distributed generation. The methodologies goals are to maximize the performance of the anti-islanding protection and minimize the incorrect operation to events of other nature, and scenarios with multiple distributed generators of different technologies are considered. At first, the main factors that affect the frequency and voltage-based protection will be explored, such as load distribution, power factor and unbalanced loads. This analysis aims to identify the most critical cases of islanding detection. The second contribution of this thesis is the Setting Map methodology, which is a graphical analysis whose effectiveness has been proved by case studies, showing to be able to improve the sensitivity of anti-islanding protection, minimizing the chances of incorrect operation. In sequence, is presented an automatic method to adjust the protection functions and voltage blocking and other based on adaptive protection. Both methods are based on the Setting Map methodology. The results indicate that it is possible to improve the islanding detection and reduce the incorrect actuation when it is used the proposed methodologies.
5

Metodologias de ajuste das proteções anti-ilhamento de geradores distribuídos considerando múltiplos eventos / Methodology to adjust distributed generation anti-islanding protections based on multiple events

Daniel Motter 16 November 2017 (has links)
Os geradores distribuídos em sistemas de distribuição de energia elétrica devem ser desconectados em eventos de ilhamento, que ocorrem quando parte da rede elétrica torna-se eletricamente isolada da concessionária e o subsistema isolado continua a ser energizado pela geração distribuída. A proteção anti-ilhamento deve detectar tal condição operativa, porém pode não atuar em condições de pequenos desbalanços entre carga e geração, ou atuar incorretamente para eventos de outra natureza. Assim, um ajuste adequado dessa proteção deve desconectar o gerador rapidamente quando detecta o ilhamento e, simultaneamente, deve ser imune a eventos como curtos-circuitos e chaveamentos de carga, por exemplo. Esta pode ser uma tarefa muito difícil face às variações de carga e diferentes eventos de não ilhamento que podem ocorrer no sistema de distribuição. Portanto, nesta tese são propostas metodologias de ajuste das funções de proteção anti-ilhamento de sub/sobrefrequência, taxa de variação de frequência, salto de vetor e sub/sobretensão, que são técnicas convencionalmente utilizadas para a detecção de ilhamento de geração distribuída. O objetivo das metodologias é maximizar a detecção de ilhamento e minimizar a atuação incorreta, e são considerados cenários com múltiplos geradores distribuídos de diferentes tecnologias. Inicialmente, são explorados os principais fatores que afetam as proteções, tais como distribuição das cargas, fator de potência e desequilíbrio das cargas. Esta análise permite identificar os casos mais difíceis de detecção de ilhamento. Como segunda contribuição, foi proposta a metodologia de análise gráfica denominada Mapa de Ajustes, cuja eficácia foi comprovada por meio de casos de teste, mostrando ser capaz de melhorar a sensibilidade da proteção anti-ilhamento e minimizar atuação incorreta. Na sequência, é apresentado um método automático para ajuste e bloqueio de tensão e outro baseado em proteção adaptativa para ajuste das funções de proteção. Ambos são baseados na metodologia de mapa de ajustes. Os resultados indicam que é possível melhorar a detecção de ilhamento e diminuir a atuação incorreta quando utilizadas as metodologias propostas. / Distributed generators in power distribution systems must be disconnected after an islanding event, which occurs when part of the power grid becomes electrically isolated from the utility and the isolated subsystem continues to be energized by the distributed generation. The antiislanding protection has to detect such operating condition, which may fail for critical loading conditions, or operate incorrectly for events of other nature than islanding. Therefore, an appropriate protection setting should quickly disconnect the generator when an islanding event is detected, and simultaneously, must be immune to events such as short circuits and load switches. This can be a very difficult task due to load variations and different nonislanding events that may occur in the distribution system. Therefore, in this thesis is proposed methodologies to adjust the anti-islanding protection functions of under/overfrequency, rate of change of frequency, vector surge and under/overvoltage, which are techniques conventionally used for islanding detection of distributed generation. The methodologies goals are to maximize the performance of the anti-islanding protection and minimize the incorrect operation to events of other nature, and scenarios with multiple distributed generators of different technologies are considered. At first, the main factors that affect the frequency and voltage-based protection will be explored, such as load distribution, power factor and unbalanced loads. This analysis aims to identify the most critical cases of islanding detection. The second contribution of this thesis is the Setting Map methodology, which is a graphical analysis whose effectiveness has been proved by case studies, showing to be able to improve the sensitivity of anti-islanding protection, minimizing the chances of incorrect operation. In sequence, is presented an automatic method to adjust the protection functions and voltage blocking and other based on adaptive protection. Both methods are based on the Setting Map methodology. The results indicate that it is possible to improve the islanding detection and reduce the incorrect actuation when it is used the proposed methodologies.
6

Inversor integrado Cuk para aproveitamento da energia fotovoltaica em conexão com a rede em corrente alternada /

Benites Quispe, Jhon Brajhan January 2019 (has links)
Orientador: Carlos Alberto Canesin / Resumo: Considerando o atual crescimento dos sistemas baseados em fontes de energia renováveis para a Geração Distribuída (GD), novas estruturas de potência estão sendo desenvolvidas para os sistemas de conversão. O presente estudo propõe a utilização do Inversor Integrado Cuk para o processamento da energia solar fotovoltaica proveniente de um conjunto de módulos fotovoltaicos. Este inversor é o resultado da integração de um conversor Cuk e um inversor de ponte completa, sendo capaz de realizar as funções de elevação e redução de tensão, e a função de converter a corrente continua em alternada, possuindo um grande potencial para a obtenção de uma estrutura de potência de reduzido volume e alto rendimento, garantindo uma baixa distorção harmônica da corrente injetada à rede. Neste trabalho de dissertação são apresentadas as análises quantitativa e qualitativa do inversor com o objetivo de mostrar em detalhes o seu funcionamento e apresentar as principais equações elétricas dos componentes reativos e semicondutores. Além disso, para a obtenção do modelo dinâmico em pequeno sinal do inversor, o método de média do circuito e modelagem média de interruptores é utilizado a fim de projetar os controladores do modo de controle adotado, o qual consiste em dois laços de corrente retroalimentados. Por outro lado, uma comparação das diferentes configurações de módulos fotovoltaicos conectados ao inversor é realizada através dos dados de simulação, a fim de obter a configuração com as melhores c... (Resumo completo, clicar acesso eletrônico abaixo) / Abstract: Considering the current growth of the renewable energy sources-based systems for Distributed Generation (DG), new power structures are being developed for the conversion systems. The present study proposes the use of the Cuk Integrated Inverter for the processing of photovoltaic solar energy from a set of photovoltaic modules. This inverter is the result of the integration of a Cuk converter and a Full Bridge inverter, being able to perform the functions of raise and reduce voltage, and the function of converting the direct current (DC) to alternating current (AC), possessing a great potential for obtaining a power structure of reduced volume and high performance, guaranteeing a low harmonic distortion of the current injected into the electric grid. In this research work, the quantitative and qualitative analysis of the inverter are presented in order to show in detail its operation and present the main electrical equations of the reactive and semiconductor components. In addition, to obtain the dynamic model in small signal of the inverter, the method of Circuit Averaging and Averaged Switch Modeling is used in order to design the controllers of the adopted control mode, which consists of two feedback loops of current. On the other hand, a comparison of the different configurations of photovoltaic modules connected to the inverter is performed by simulation data, in order to obtain the configuration with the best performance characteristics of the system. The maximum power p... (Complete abstract click electronic access below) / Mestre
7

Mitigação de variações de tensão causadas pela proteção anti-ilhamento de geradores distribuídos via controle de taps de reguladores de tensão / Mitigating voltage variations caused by the anti-islanding protection of distributed generator via voltage regulator tap control

Lima, Daniel Ferreira 04 August 2017 (has links)
A conexão de geradores distribuídos em sistemas de distribuição deve ser cuidadosamente avaliada para que os mesmos auxiliem efetivamente na melhoria do desempenho das redes elétricas, buscando reduzir ou eliminar eventuais situações que causem a degradação da qualidade da energia elétrica fornecida aos consumidores, entre outros aspectos. Neste contexto, existem vários trabalhos que analisam a influência da conexão de geradores distribuídos no perfil de tensão da rede elétrica, frequência, desequilíbrio de fases e distorção harmônica. No entanto, há poucos trabalhos analisando os efeitos da desconexão de geradores distribuídos na qualidade da energia fornecida aos consumidores. Uma vez operando em paralelo com a rede de distribuição, esses geradores influenciam o perfil de tensão e o comportamento dos dispositivos reguladores de tensão. Como consequência, sua desconexão pode provocar variações de tensão intensas causando danos ou mau funcionamento às cargas. A desconexão pode ser repentina ou devido à atuação da proteção anti-ilhamento, seguida dos procedimentos de religamento automático do alimentador, se houver. Visando estudar este problema, o qual tende a se tornar uma nova preocupação das concessionárias de energia elétrica, e no intuito de minimizar e/ou eliminar os possíveis efeitos negativos dessas variações de tensão, esta pesquisa propõe o desenvolvimento de um método de controle dos taps dos reguladores de tensão. Neste método, o controle dos taps foi modelado como um problema de otimização, minimizando as violações de tensão mencionadas anteriormente e também a quantidade de operações dos reguladores de tensão ao longo de um dia típico. A otimização foi solucionada com um Algoritmo Genético e os resultados obtidos indicaram que é possível minimizar as variações de tensão usando a curva de carga do sistema para planejar a operação dos reguladores de tensão. / The connection of distributed generators in an electric power system should be evaluated carefully to ensure that they effectively assist in improving the performance of electrical networks, reducing or eliminating any situations that cause degradation of the power quality of the consumers, and other issues. In this context, there are several studies that analyze the influence of generators connected to distribution systems and how they affect the frequency, cause variations in voltage magnitude, voltage unbalance and harmonic distortion. However, there are a few studies analyzing the effects that the disconnection of distributed generators induces to the power quality of consumers. Once operating in parallel with the distribution network, these generators have an effect on voltage variations and voltage regulator devices. As a result, disconnection can cause severe voltage variations causing damage or malfunction to the loads. The disconnection may be sudden or due to the action of anti-islanding protection, followed by the procedure to reconnect the substation, if it is possible. In order to study this problem, which tends to become a new power quality concern for electric utilities, and in order to minimize and / or eliminate the possible side effects of the voltage variations, this research proposes the development of a control method of voltage regulators\' taps. In this method, the control of taps was modeled as an optimization problem which aimed to minimize these voltage variations aforementioned and also the amount of voltage regulator operations over a typical day. The optimization was solved by a Genetic Algorithm and the results obtained demonstrate that it is possible to minimize the voltage variation by using the system load curve to plan the operation of voltage regulators.
8

Estudo sobre a interação de métodos anti-ilhamento para sistemas fotovoltaicos conectados à rede de distribuição de baixa tensão com múltiplos inversores. / Study about the interation of anti-islanding methods for photovoltaic systems connected to the low voltage distribution grid with multiple inverters.

Silva, Humberto Trindade da 30 March 2016 (has links)
Este trabalho estuda a interação entre os métodos anti-ilhamento aplicados em sistemas fotovoltaicos residenciais, operando simultaneamente em uma rede de distribuição de baixa tensão. Os sistemas fotovoltaicos em geral interagem entre si, com a rede de distribuição da concessionária e com outras fontes de geração distribuída. Uma consequência importante dessa interação é a ocorrência do ilhamento, que acontece quando as fontes de geração distribuída fornecem energia ao sistema elétrico de potência mesmo quando esta se encontra eletricamente isolada do sistema elétrico principal. A função anti-ilhamento é uma proteção extremamente importante, devendo estar presente em todos os sistemas de geração distribuída. Atualmente, são encontradas diversas técnicas na literatura. Muitas delas oferecem proteção adequada quando um inversor está conectado à linha de distribuição, mas podem falhar quando dois ou mais funcionam simultaneamente, conectados juntos ou próximos entre si. Dois destes métodos são analisados detalhadamente nesse estudo, avaliados em uma rede de distribuição residencial de baixa tensão. Os resultados obtidos mostram que a influência de um método sobre o outro é dependente da predominância de cada um deles dentro do sistema elétrico. Contudo, nas condições analisadas o ilhamento foi detectado dentro do limite máximo estabelecido pelas normas pertinentes. / This work studies the interaction between islanding detection methods applied in residential photovoltaic systems, operating simultaneously in a low voltage distribution network. Photovoltaic systems, in general, interact with themselves, with the utility grid and other distributed generation sources. An important consequence of this interaction is the islanding occurrence, which happens when distributed generation sources supply energy to the electrical power system even when it is electrically isolated from the main electrical system. The anti-islanding function is an extremely important protection, and should be present in all distributed generation systems. Actually, many techniques are found in the literature. Most of them provide suitable protection when one inverter is connected to the distribution line, but can fail when two or more work simultaneously, connected at the same point or close to each other. Two of these methods are analyzed in detail in this study and evaluated in a residential low voltage distribution line. The obtained results show that the influence of a method over another one is dependent of the predominance of each one within the electrical system. However, in the analyzed condition the islanding was detected within the maximum allowed time established by applicable rules.
9

Mitigação de variações de tensão causadas pela proteção anti-ilhamento de geradores distribuídos via controle de taps de reguladores de tensão / Mitigating voltage variations caused by the anti-islanding protection of distributed generator via voltage regulator tap control

Daniel Ferreira Lima 04 August 2017 (has links)
A conexão de geradores distribuídos em sistemas de distribuição deve ser cuidadosamente avaliada para que os mesmos auxiliem efetivamente na melhoria do desempenho das redes elétricas, buscando reduzir ou eliminar eventuais situações que causem a degradação da qualidade da energia elétrica fornecida aos consumidores, entre outros aspectos. Neste contexto, existem vários trabalhos que analisam a influência da conexão de geradores distribuídos no perfil de tensão da rede elétrica, frequência, desequilíbrio de fases e distorção harmônica. No entanto, há poucos trabalhos analisando os efeitos da desconexão de geradores distribuídos na qualidade da energia fornecida aos consumidores. Uma vez operando em paralelo com a rede de distribuição, esses geradores influenciam o perfil de tensão e o comportamento dos dispositivos reguladores de tensão. Como consequência, sua desconexão pode provocar variações de tensão intensas causando danos ou mau funcionamento às cargas. A desconexão pode ser repentina ou devido à atuação da proteção anti-ilhamento, seguida dos procedimentos de religamento automático do alimentador, se houver. Visando estudar este problema, o qual tende a se tornar uma nova preocupação das concessionárias de energia elétrica, e no intuito de minimizar e/ou eliminar os possíveis efeitos negativos dessas variações de tensão, esta pesquisa propõe o desenvolvimento de um método de controle dos taps dos reguladores de tensão. Neste método, o controle dos taps foi modelado como um problema de otimização, minimizando as violações de tensão mencionadas anteriormente e também a quantidade de operações dos reguladores de tensão ao longo de um dia típico. A otimização foi solucionada com um Algoritmo Genético e os resultados obtidos indicaram que é possível minimizar as variações de tensão usando a curva de carga do sistema para planejar a operação dos reguladores de tensão. / The connection of distributed generators in an electric power system should be evaluated carefully to ensure that they effectively assist in improving the performance of electrical networks, reducing or eliminating any situations that cause degradation of the power quality of the consumers, and other issues. In this context, there are several studies that analyze the influence of generators connected to distribution systems and how they affect the frequency, cause variations in voltage magnitude, voltage unbalance and harmonic distortion. However, there are a few studies analyzing the effects that the disconnection of distributed generators induces to the power quality of consumers. Once operating in parallel with the distribution network, these generators have an effect on voltage variations and voltage regulator devices. As a result, disconnection can cause severe voltage variations causing damage or malfunction to the loads. The disconnection may be sudden or due to the action of anti-islanding protection, followed by the procedure to reconnect the substation, if it is possible. In order to study this problem, which tends to become a new power quality concern for electric utilities, and in order to minimize and / or eliminate the possible side effects of the voltage variations, this research proposes the development of a control method of voltage regulators\' taps. In this method, the control of taps was modeled as an optimization problem which aimed to minimize these voltage variations aforementioned and also the amount of voltage regulator operations over a typical day. The optimization was solved by a Genetic Algorithm and the results obtained demonstrate that it is possible to minimize the voltage variation by using the system load curve to plan the operation of voltage regulators.
10

Estudo sobre a interação de métodos anti-ilhamento para sistemas fotovoltaicos conectados à rede de distribuição de baixa tensão com múltiplos inversores. / Study about the interation of anti-islanding methods for photovoltaic systems connected to the low voltage distribution grid with multiple inverters.

Humberto Trindade da Silva 30 March 2016 (has links)
Este trabalho estuda a interação entre os métodos anti-ilhamento aplicados em sistemas fotovoltaicos residenciais, operando simultaneamente em uma rede de distribuição de baixa tensão. Os sistemas fotovoltaicos em geral interagem entre si, com a rede de distribuição da concessionária e com outras fontes de geração distribuída. Uma consequência importante dessa interação é a ocorrência do ilhamento, que acontece quando as fontes de geração distribuída fornecem energia ao sistema elétrico de potência mesmo quando esta se encontra eletricamente isolada do sistema elétrico principal. A função anti-ilhamento é uma proteção extremamente importante, devendo estar presente em todos os sistemas de geração distribuída. Atualmente, são encontradas diversas técnicas na literatura. Muitas delas oferecem proteção adequada quando um inversor está conectado à linha de distribuição, mas podem falhar quando dois ou mais funcionam simultaneamente, conectados juntos ou próximos entre si. Dois destes métodos são analisados detalhadamente nesse estudo, avaliados em uma rede de distribuição residencial de baixa tensão. Os resultados obtidos mostram que a influência de um método sobre o outro é dependente da predominância de cada um deles dentro do sistema elétrico. Contudo, nas condições analisadas o ilhamento foi detectado dentro do limite máximo estabelecido pelas normas pertinentes. / This work studies the interaction between islanding detection methods applied in residential photovoltaic systems, operating simultaneously in a low voltage distribution network. Photovoltaic systems, in general, interact with themselves, with the utility grid and other distributed generation sources. An important consequence of this interaction is the islanding occurrence, which happens when distributed generation sources supply energy to the electrical power system even when it is electrically isolated from the main electrical system. The anti-islanding function is an extremely important protection, and should be present in all distributed generation systems. Actually, many techniques are found in the literature. Most of them provide suitable protection when one inverter is connected to the distribution line, but can fail when two or more work simultaneously, connected at the same point or close to each other. Two of these methods are analyzed in detail in this study and evaluated in a residential low voltage distribution line. The obtained results show that the influence of a method over another one is dependent of the predominance of each one within the electrical system. However, in the analyzed condition the islanding was detected within the maximum allowed time established by applicable rules.