• Refine Query
  • Source
  • Publication year
  • to
  • Language
  • 7
  • 1
  • Tagged with
  • 9
  • 9
  • 6
  • 6
  • 6
  • 6
  • 6
  • 4
  • 4
  • 4
  • 3
  • 2
  • 2
  • 2
  • 2
  • About
  • The Global ETD Search service is a free service for researchers to find electronic theses and dissertations. This service is provided by the Networked Digital Library of Theses and Dissertations.
    Our metadata is collected from universities around the world. If you manage a university/consortium/country archive and want to be added, details can be found on the NDLTD website.
1

Modeling a run-around heat and moisture exchanger using two counter/cross flow exchangers

Vali, Alireza 29 June 2009
In this study, a numerical model is developed for determining coupled heat and moisture transfer in a run-around membrane energy exchanger (RAMEE) using two counter/cross flow exchangers and with a salt solution of MgCl2 as the coupling fluid. The counter/cross flow exchanger is a counter-flow exchanger with cross-flow inlet and outlet headers. The model is two-dimensional, steady-state and based on the physical principles of conservation of momentum, energy, and mass. The finite difference method is used in this model to discretize the governing equations.<p> The heat transfer model is validated with effectiveness correlations in the literature. It is shown that the difference between the numerical model and correlations is less than ¡À2% and ¡À2.5% for heat exchangers and run around heat exchangers (RAHE), respectively. The simultaneous heat and moisture transfer model is validated with data from another model and experiments. The inter-model comparison shows a difference of less than 1%. The experimental validation shows an average discrepancy of 1% to 17% between the experimental and numerical data for overall total effectiveness. At lower NTUs the numerical and experimental results show better agreement (e.g. within 1-4% at NTU=4).<p> The model for RAHE is used to develop new effectiveness correlations for the geometrically more complex counter/cross flow heat exchangers and RAHE systems. The correlations are developed to predict the response of the exchangers and overall system to the change of different design characteristics as it is determined by the model. Discrepancies between the simulated and correlated results are within ¡À2% for both the heat exchangers and the RAHE systems.<p> It is revealed by the model that the overall effectiveness of the counter/cross flow RAMEE depends on the entrance ratio (the ratio of the length of the inlet and outlet headers to the length of the exchanger, xi/x0), aspect ratio (the ratio of the height to the length of the exchanger, y0/x0), number of heat transfer units (NTU), heat capacity rate ratio (Cr*), number of mass transfer units (NTUm), and the mass flow rate ratio of pure salt in desiccant solution to dry air (m*). Beside these dimensionless parameters, the performance of the RAMEE system is affected by the liquid-air flow configuration and the operating inlet temperature and humidity.<p> This study concludes that the maximum effectiveness of the RAMEE system with two counter/cross flow exchangers occurs when NTU and NTUm are large (e.g. greater than 10). At any NTU, the overall effectiveness of the RAMEE system increases with Cr* until it reaches a maximum value when Cr*= . Increasing Cr* above causes the overall effectiveness to decrease slightly. Therefore, to achieve the maximum overall effectiveness of the system, Cr* must be close to . is a function of NTU and operating conditions e.g., with NTU=10, and under AHRI summer and winter operating conditions, respectively. The exchangers in the RAMEE system are needed to have a small aspect ratio (e.g. y0/x0<0.2) and small entrance ratio (e.g. xi/x0<0.1) to get the maximum overall effectiveness of a RAMEE system using two counter/cross flow exchangers. Such a RAMEE system has a total effectiveness 6% higher and 1.5% lower compared to the same cross-flow and counter-flow RAMEE, respectively (at NTU=10, Cr*¡Ö3, y0/x0=0.2 and xi/x0=0.1).
2

The impacts of outdoor air conditions and non-uniform exchanger channels on a run around membrane energy exchanger

Hemingson, Howard B 25 February 2011
This thesis contains the numerically investigations of the performance of a run-around membrane energy exchanger (RAMEE) at different outdoor air conditions and the effects of non-uniform exchanger channels. The RAMEE is a new type of building ventilation air energy recovery system that allows heat and moisture to be transferred between isolated supply and exhaust air streams. Two liquid-to-air membrane energy exchangers (LAMEEs) are placed in the supply and exhaust air ducts and transfer heat and moisture between air and a circulating liquid desiccant that couples the two LAMEEs together. The ability of the system to transfer heat and moisture between isolated supply and exhaust ducts makes it appropriate for numerous HVAC applications (e.g., hospitals and building energy retrofits). <p> The performance of the RAMEE at different outdoor air conditions is shown to be highly variable due to the coupling of the heat and moisture transfer by the desiccant. This coupling allows the humidity ratio between the indoor and outdoor air to influence the heat transfer and the moisture transfer is influenced by the difference between the indoor and outdoor air temperatures. The coupling produces some complex RAMEE performance characteristics at some outdoor air conditions where the effectiveness values (i.e., sensible, latent, and total) were shown to be less than 0% or greater than 100%. Effectiveness and operating correlations are developed to describe these complex behaviours because existing correlations do not account for the coupling effects. The correlations can serve as design and operation tools for the RAMEE which do not require the use of an iterative computational numerical model.<p> Non-uniform exchanger channels are present in the RAMEE because of pressure differences between the air and solution channels which deform the membrane into the air channel. The non-uniform channels are analytically shown to create maldistributed fluid flows and variable heat and mass transfer coefficients. The combined effects of these two changes lead to a reduction in the RAMEE effectiveness, which increases as the size of the membrane deformation increases. The reduction in total effectiveness for an exchanger where the membrane has a peak deflection of 10% of the nominal air channel thickness operating at a NTU of 12 was shown to be 12.5%. These results of non-uniform exchanger channels agree with previously conducted experimental results.
3

Modeling the transient behavior of a run-around heat and moisture exchanger system

Seyed Ahmadi, Mehran 25 November 2008
In this thesis, a numerical model for coupled heat and moisture transfer in a run around membrane energy exchanger (RAMEE) with a liquid desiccant as a coupling fluid is developed. The numerical model is two dimensional, transient and is formulated using the finite difference method with an implicit time discretization. The model for the case of only heat transfer for a single heat exchanger is compared to an available analytical solution and good agreement is obtained. It is shown that the discrepancy between the numerical and theoretical dimensionless bulk outlet temperature of the fluids is less than 4% during the transient period. The model is also validated for the case of simultaneous heat and moisture transfer using experimental data measured during the laboratory testing of a RAMEE system. The results for both sensible and latent effectiveness showed satisfactory agreement at different operating conditions. However, there are some discrepancies between the simulation and the experimental data during the transient times. It is proposed that these discrepancies may be due to experimental flow distribution problems within the exchanger. The maximum average absolute differences between the measured and simulated transient effectivenesses were 7.5% and 10.3% for summer and winter operating conditions, respectively.<p> The transient response of the RAMEE system for step changes in the inlet supply air temperature and humidity ratio is presented using the numerical model. In addition, the system quasi steady state operating conditions are predicted as the system approaches its steady state operating condition. The effect of various dimensionless parameters on the transient response is predicted separately. These included: the number of heat transfer units, thermal capacity ratio, heat loss/gain ratio, storage volume ratio and the normalized initial salt solution concentration. It is shown that the initial salt solution concentration and the storage volume of the salt solution have significant impacts on the transient response of the system and the heat loss/gain rates from/to the circulated fluid flow can change the system quasi steady effectiveness substantially. The detailed study of the transient performance of the RAMEE is useful to determine the transient response time of the system under different practical situations.
4

The impacts of outdoor air conditions and non-uniform exchanger channels on a run around membrane energy exchanger

Hemingson, Howard B 25 February 2011 (has links)
This thesis contains the numerically investigations of the performance of a run-around membrane energy exchanger (RAMEE) at different outdoor air conditions and the effects of non-uniform exchanger channels. The RAMEE is a new type of building ventilation air energy recovery system that allows heat and moisture to be transferred between isolated supply and exhaust air streams. Two liquid-to-air membrane energy exchangers (LAMEEs) are placed in the supply and exhaust air ducts and transfer heat and moisture between air and a circulating liquid desiccant that couples the two LAMEEs together. The ability of the system to transfer heat and moisture between isolated supply and exhaust ducts makes it appropriate for numerous HVAC applications (e.g., hospitals and building energy retrofits). <p> The performance of the RAMEE at different outdoor air conditions is shown to be highly variable due to the coupling of the heat and moisture transfer by the desiccant. This coupling allows the humidity ratio between the indoor and outdoor air to influence the heat transfer and the moisture transfer is influenced by the difference between the indoor and outdoor air temperatures. The coupling produces some complex RAMEE performance characteristics at some outdoor air conditions where the effectiveness values (i.e., sensible, latent, and total) were shown to be less than 0% or greater than 100%. Effectiveness and operating correlations are developed to describe these complex behaviours because existing correlations do not account for the coupling effects. The correlations can serve as design and operation tools for the RAMEE which do not require the use of an iterative computational numerical model.<p> Non-uniform exchanger channels are present in the RAMEE because of pressure differences between the air and solution channels which deform the membrane into the air channel. The non-uniform channels are analytically shown to create maldistributed fluid flows and variable heat and mass transfer coefficients. The combined effects of these two changes lead to a reduction in the RAMEE effectiveness, which increases as the size of the membrane deformation increases. The reduction in total effectiveness for an exchanger where the membrane has a peak deflection of 10% of the nominal air channel thickness operating at a NTU of 12 was shown to be 12.5%. These results of non-uniform exchanger channels agree with previously conducted experimental results.
5

Modeling the transient behavior of a run-around heat and moisture exchanger system

Seyed Ahmadi, Mehran 25 November 2008 (has links)
In this thesis, a numerical model for coupled heat and moisture transfer in a run around membrane energy exchanger (RAMEE) with a liquid desiccant as a coupling fluid is developed. The numerical model is two dimensional, transient and is formulated using the finite difference method with an implicit time discretization. The model for the case of only heat transfer for a single heat exchanger is compared to an available analytical solution and good agreement is obtained. It is shown that the discrepancy between the numerical and theoretical dimensionless bulk outlet temperature of the fluids is less than 4% during the transient period. The model is also validated for the case of simultaneous heat and moisture transfer using experimental data measured during the laboratory testing of a RAMEE system. The results for both sensible and latent effectiveness showed satisfactory agreement at different operating conditions. However, there are some discrepancies between the simulation and the experimental data during the transient times. It is proposed that these discrepancies may be due to experimental flow distribution problems within the exchanger. The maximum average absolute differences between the measured and simulated transient effectivenesses were 7.5% and 10.3% for summer and winter operating conditions, respectively.<p> The transient response of the RAMEE system for step changes in the inlet supply air temperature and humidity ratio is presented using the numerical model. In addition, the system quasi steady state operating conditions are predicted as the system approaches its steady state operating condition. The effect of various dimensionless parameters on the transient response is predicted separately. These included: the number of heat transfer units, thermal capacity ratio, heat loss/gain ratio, storage volume ratio and the normalized initial salt solution concentration. It is shown that the initial salt solution concentration and the storage volume of the salt solution have significant impacts on the transient response of the system and the heat loss/gain rates from/to the circulated fluid flow can change the system quasi steady effectiveness substantially. The detailed study of the transient performance of the RAMEE is useful to determine the transient response time of the system under different practical situations.
6

Modeling a run-around heat and moisture exchanger using two counter/cross flow exchangers

Vali, Alireza 29 June 2009 (has links)
In this study, a numerical model is developed for determining coupled heat and moisture transfer in a run-around membrane energy exchanger (RAMEE) using two counter/cross flow exchangers and with a salt solution of MgCl2 as the coupling fluid. The counter/cross flow exchanger is a counter-flow exchanger with cross-flow inlet and outlet headers. The model is two-dimensional, steady-state and based on the physical principles of conservation of momentum, energy, and mass. The finite difference method is used in this model to discretize the governing equations.<p> The heat transfer model is validated with effectiveness correlations in the literature. It is shown that the difference between the numerical model and correlations is less than ¡À2% and ¡À2.5% for heat exchangers and run around heat exchangers (RAHE), respectively. The simultaneous heat and moisture transfer model is validated with data from another model and experiments. The inter-model comparison shows a difference of less than 1%. The experimental validation shows an average discrepancy of 1% to 17% between the experimental and numerical data for overall total effectiveness. At lower NTUs the numerical and experimental results show better agreement (e.g. within 1-4% at NTU=4).<p> The model for RAHE is used to develop new effectiveness correlations for the geometrically more complex counter/cross flow heat exchangers and RAHE systems. The correlations are developed to predict the response of the exchangers and overall system to the change of different design characteristics as it is determined by the model. Discrepancies between the simulated and correlated results are within ¡À2% for both the heat exchangers and the RAHE systems.<p> It is revealed by the model that the overall effectiveness of the counter/cross flow RAMEE depends on the entrance ratio (the ratio of the length of the inlet and outlet headers to the length of the exchanger, xi/x0), aspect ratio (the ratio of the height to the length of the exchanger, y0/x0), number of heat transfer units (NTU), heat capacity rate ratio (Cr*), number of mass transfer units (NTUm), and the mass flow rate ratio of pure salt in desiccant solution to dry air (m*). Beside these dimensionless parameters, the performance of the RAMEE system is affected by the liquid-air flow configuration and the operating inlet temperature and humidity.<p> This study concludes that the maximum effectiveness of the RAMEE system with two counter/cross flow exchangers occurs when NTU and NTUm are large (e.g. greater than 10). At any NTU, the overall effectiveness of the RAMEE system increases with Cr* until it reaches a maximum value when Cr*= . Increasing Cr* above causes the overall effectiveness to decrease slightly. Therefore, to achieve the maximum overall effectiveness of the system, Cr* must be close to . is a function of NTU and operating conditions e.g., with NTU=10, and under AHRI summer and winter operating conditions, respectively. The exchangers in the RAMEE system are needed to have a small aspect ratio (e.g. y0/x0<0.2) and small entrance ratio (e.g. xi/x0<0.1) to get the maximum overall effectiveness of a RAMEE system using two counter/cross flow exchangers. Such a RAMEE system has a total effectiveness 6% higher and 1.5% lower compared to the same cross-flow and counter-flow RAMEE, respectively (at NTU=10, Cr*¡Ö3, y0/x0=0.2 and xi/x0=0.1).
7

Study of Extended-gate FET-based Microsensor for Detecting the Carbon Dioxide in Water

Chen , Po-Han 30 July 2012 (has links)
The large carbon dioxides produced by highly developed industries not only result in serious air pollution and health problems, but also cause ocean acidification and decrease the survival rate of fry in aquaculture. Therefore, to develop a system for real-time detection of the concentration of carbon dioxide in aquaculture has become a very important research issue. Optical analysis and gas-chromatography are the two main methods adopted in conventional gas detection. Although the conventional carbon dioxide detectors presented high sensitivity and accuracy, the high fabrication cost, large dimension, low capability of batch fabrication and without real-time monitoring function will limit their applications. This thesis utilizes MEMS technology to implement an extended-gate field-effect transistor (EGFET) with an integrated gas permeable membrane for development of a high-sensitivity, small size and low cost carbon dioxide microsensor. The main material of the carbon dioxide gas permeable membrane adopted in this research is dioctyl sebacate. The main processing steps of the proposed microsensor include four photolithography and four thin-film deposition processes. In addition, the influences of the channel width/length ratio of EGFET and the coating of gas permeable membrane on the sensing performances of presented microsensor are also investigated in this study. The chip size of the implemented carbon dioxide microsensor is 11 mm¡Ñ13 mm¡Ñ 0.5 mm and the sensing area is 1 mm¡Ñ1 mm. As the carbon dioxide concentration varies from 0.25 mM to 50 mM, a very high sensitivity (42.3 mV/ppm) and sensing linearity (99.2%) of the proposed EGFET microsensor can be demonstrated. In addition, the response time of the presented carbon dioxide microsensor is only about 100 seconds, hence it is very suitable for developing a real-time monitoring microsystem.
8

Investigation and Evaluation of a Bi-Polar Membrane Based Seawater Concentration Cell and Its Suitability as a Low Power Energy Source for Energy Harvesting/MEMS Devices

Merz, Clifford Ronald 27 October 2008 (has links)
It has long been known from Thermodynamics and written in technical literature that, in principal, instant energy can be made available when dilute and concentrated solutions are mixed. For example, a river flowing into the sea carries with it a physical-chemical potential energy in its low salt content, some of which should be recoverable. As also known, a naturally occurring, diffusion-driven, spontaneous transport of ions occurs throughout a solution matrix, thru barrier interfaces, or thru ion-selective membranes from the side containing the salts of higher concentration to the compartments containing the more dilute solution to effect the equalization of concentration of the ionic species. Since this ion movement consists, preferentially, of either cations or anions, it leads to a charge separation and potential difference across the membrane, otherwise known as a membrane potential. Eventually, when the concentrations in the compartment are the same, the cell ceases to function. However, if operated as a fuel cell with its respective concentrations continually replenished, equilibrium at a specific value of potential difference is established. To capture the energy of this potentially significant albeit low power energy source, a suitable energy extraction device is required. The focus of this Ph.D. research effort is to address the concept, research and evaluation of a Bi-Polar membrane based seawater concentration cell and its suitability as a low power energy source for Energy Harvesting/MEMS devices (patent pending).
9

IMPLEMENTATION OF NITROGEN RECOVERY AT WASTEWATER TREATMENT PLANTS TO COMPLEMENT ARTIFICIAL FERTILISER PRODUCTION : An investigation of the nitrogen recovery potential, energy consumption and environmental impacts at Kungsängens wastewater treatment plant in Västerås, Sweden

Kestran, Cassandra, Larsson, Olivia January 2023 (has links)
As Kungsängens wastewater treatment plant is considering a move, it opens up a possibility to implement nitrogen recovery technologies that comply with current and future legislative requirements. Nitrogen recovery offers simultaneous treatment of wastewater and collection of concentrated ammonia products for fertiliser production. This can create a circular and sustainable solution by reduced energy consumption, greenhouse gas emissions and nitrogen pollution. Despite the large amount of research that has been performed on this topic, practical use at wastewater treatment facilities in Sweden are still scarce. The aim of the degree project was to identify nitrogen recovery technologies and investigate their potential impact at a new Kungsängens wastewater treatment plant. A literature review provided different nitrogen technologies and concept scoring was used to rank and score them. Gas permeable membrane and ammonia stripping ranked the highest and both have the potential to be implemented at Kungsängens current or possible new site. Simulations were used to identify the change in energy consumption and change in effluent water quality related to the implementation of a nitrogen recovery technology. Calculations were performed to reach thequantities of nitrogen that could be recovered, and it was found that the nitrogen recovery potential was 0,2343 ton/d using gas permeable membrane, and 0,2750 ton/d using ammonia stripping. By replacing artificial fertilisers with recovered nitrogen, 7,95 kWh/kg N could be saved using gas permeable membrane and 2,76 kWh/kg N could be saved using ammonia stripping. The degree project also provides insight into European and Swedish lawconformity and predictability. Finally, a discussion of environmental impacts, potential for nitrogen recovery, nitrogen policies, and energy savings was conducted. It was concluded that nitrogen recovery can create benefits due to avoided nitrous oxide emissions, avoided production of precipitation chemicals and decreased energy consumption for aeration. Compared to artificial fertiliser produced using the Haber-Bosch method, it was determined that a significant reduction of carbon dioxide emissions could be reached.

Page generated in 0.0696 seconds