Spelling suggestions: "subject:"clynamics simulator"" "subject:"ctynamics simulator""
1 |
FDS modelling of hot smoke testing, cinema and airport concourseWebb, Alex K. January 2006 (has links)
Thesis (M.S.) -- Worcester Polytechnic Institute. / Keywords: Hot smoke test; FDS; CFD; Computer modelling. Includes bibliographical references (p.105-110).
|
2 |
Simulation and Integration of a 6-DOF Controllable Multirotor VehicleDeans, Collin Andrew 07 August 2020 (has links)
The purpose of this thesis is to develop an existing design of a fully controllable multi-rotor vehicle toward simulating small satellite dynamics, enabling technology development to be accelerated and component failure risks to be mitigated by providing a testing platform with dynamics similar to those of small satellites in orbit. Evaluating dynamics-sensitive software and hardware components for use in small satellite operations has typically been relegated to simulated or physically constrained testing environments. More recently, researchers have begun using multi-rotor aerial vehicles to mimic the orbital motion of such satellites, further increasing simulation fidelity. The dynamical nature of multi-rotor vehicles allows them to accurately simulate the translational dynamics of a small satellite, but they struggle to accurately simulate rotational dynamics, as conventional multi-rotor vehicles' translational and rotational dynamics are coupled. In this thesis, an optimal design for a multi-rotor vehicle independently controllable in all six degrees of freedom is evaluated as a suitable simulation platform. The design of the proposed physical system is discussed and progress toward its construction is demonstrated. To facilitate future research endeavors, a simulation of the vehicle in a software-in-the-loop environment, using the Gazebo dynamics simulator, is developed and its performance evaluated. This simulation is then used to evaluate the vehicle's feasibility as a small-satellite dynamics simulator by tasking it with tracking dynamic position and attitude time histories representative of a small satellite. / Master of Science / When developing a spacecraft, it can be difficult to accurately test software and hardware that are sensitive to the spacecraft's motion. This difficulty arises because the space environment experienced by orbiting spacecraft allows them to move and rotate freely, and recreating this freedom of motion on earth requires large, expensive, and difficult-to-access test equipment. To make this testing more accessible, researchers have begun using quadcopter drones to mimic some aspects of a spacecraft's motion. While quadcopters can move like an orbiting spacecraft can, their designs do not allow them to rotate like an orbiting spacecraft can, thus providing an incomplete recreation of spacecraft motion. To correct this shortcoming, an existing drone design that is able to move and rotate simultaneously without fear of crashing is developed, with progress shown toward its construction. A software simulation of the drone is developed to help future researchers test software and algorithms before flying it on the physical drone. The simulation is then used to see how well the drone design can recreate the motions that a small spacecraft would experience.
|
3 |
Valideringsstudie av Multi-Zone Fire ModelSchagerström, Lukas January 2020 (has links)
Det finns ett flertal brandsimuleringsprogram på marknaden som används i olika utsträckning varav ett är Fire Dynamics Simulator (FDS). En av nackdelarna med FDS är att det kan ta mycket tid att göra en brandsimulering. Det finns brandsimuleringsprogram som med stor sannolikhet utför brandsimuleringar snabbare än FDS. För några av dessa brandsimuleringsprogram finns det inte någon dokumentation om hur resultaten som brandsimuleringsprogrammen producerar ställer sig mot det som skulle hända i verkligheten vid en brand, något som kallas att vara valideratdet vill säga programmen är inte validerade. Ett av dessa brandsimuleringsprogram är Multi-Zone Fire Model (MZ-Fire Model). Brandsimuleringsprogrammet MZ-Fire Model bygger på ett multizonkoncept framtaget av Suzuki et al. Multizonkonceptet har validerats i tidigare studier varav ett är en brand i tunnel men även bränder i mindre lokaler har prövats. Det finns utrymme för ökad kunskap om hur multizonkonceptet hanterar bränder i stora rumslokaler då det inte finns någon känd dokumentation kring detta. Det finns i dagsläget inte en enda studie som behandlar brandsimuleringsprogrammet MZ-Fire Model. I rapporten redogörs för simulerande av en brand i 4 olika rum av brandsimuleringsprogrammen MZ-Fire Model och FDS, dess simulerade värden är sedan jämförda mot varandra. / There are a number of fire simulation programs on the market that are used to varying degrees, one of which is Fire Dynamics Simulator (FDS). One of the disadvantages of FDS is that it can take a lot of time to do a fire simulation. There are fire simulation programs that are very likely to perform fire simulations faster than FDS. For some of these fire simulation programs, there is no documentation on how the results produced by the programs compare with what would happen in the event of a real fire, something called to bethat is they are not validated. One of these fire simulation programs is Multi-Zone Fire Model (MZ-Fire Model). The fire simulation program MZ-Fire Model is based on a multi-zone concept developed by Suzuki et al. The multi-zone concept has been validated in previous studies, one of which is a fire in a tunnel but fires in smaller premises have also been tested. There is room for increased knowledge about how the multi-zone concept handles fires in large rooms, as there is no known documentation on this. Currently, there is not a single study dealing with the MZ-Fire Model program. The report describes the simulation of a fire in 4 different rooms by the programs MZ-Fire Model and FDS, its simulated values are then compared against each other.
|
4 |
Validering av solida temperaturer i FDS genom jämförelse mot FE-beräkningar / Validating Solid Phase Temperatures in FDS by Comparison With FE-CalculationsLindqvist, Petter January 2020 (has links)
FDS (Fire Dynamics Simulator) använder en version av Navier-Stokes ekvationerna för att göra noggranna beräkningar av värme- och gastransport genom brandbelastade utrymmen. Utvecklarna av programmet arbetar kontinuerligt med att validera det allteftersom nya funktioner tillförs för att öka noggrannheten och bredda tillämpningsområdena. Väldigt lite av detta arbete fokuserar dock på FDS:s konduktionsmodell, den endimensionella Crank-Nicolson metoden. Det här examensarbetet ämnar därför undersöka noggrannheten i FDS:s konduktionsmodell genom jämförelse mot beräkningar med FEM (Finita elementmetoden). En FDS-modell skapades för att tillåta undersökning av en vägg och dess randvillkor med så liten påverkan från andra faktorer som möjligt. Detta för att skapa en kontrollerad omgivning som enkelt kunde replikeras i efterföljande FE-beräkningar av det konduktiva värmeflödet genom den solida obstruktionen. Tre väggar (10 cm betong, 20 cm betong och 1 mm stål) vardera med tre randvillkor (Exposed, Void och Insulated) utsattes för tre temperaturer (100 °C, 500 °C och 1000 °C) vilket ger 27 FDS simuleringar. Den adiabatiska yttemperaturen mättes i varje simulering och användes som indata till motsvarande FE-beräkningar. Resultatet påvisade inga signifikanta motsägelser vad gäller randvillkoren, med tillräcklig tid för termisk penetrering påverkade de den resulterande temperaturen som väntat. Undantaget var en mindre avvikelse i stålväggarna som utsattes för 100 °C och 500 °C med randvillkoren Exposed och Void där FDS aningen underskattade temperaturen relativt FE-beräkningarna. Gastemperaturerna i gridcellerna närmast väggen visade sig vara opålitliga. De tenderade att genomgå substantiella fluktuationer, troligen som ett resultat av hur FDS hanterar diskretiseringen av icke-solida volymer för Navier-Stokes beräkningarna. Dessa fluktuationer påverkade dock inte de resulterande solida temperaturerna eftersom medelgastemperaturen var korrekt. FDS påvisades även ha en tendens att aningen överskatta yttemperaturen under de första minuterna av simuleringarna relativt FE-beräkningarna. Temperaturerna från de två beräkningsmetoderna konvergerade dock efter några få minuter i samtliga tester. Dessa avvikelser ansågs ha för liten påverkan på de solida temperaturerna för att påvisa onoggrannhet i FDS. Därmed drogs slutsatsen att FDS:s beräkningar av temperaturer i solida material är tillräckligt noggranna inom dessa avgränsningar. / FDS (Fire Dynamics Simulator) uses a version of the Navier-Stokes equations to make accurate calculations of heat and gas flow through enclosures exposed to fire. The developers of FDS have, and continue to, validate it as new features get added in an attempt to increase its accuracy and broaden its potential applications. However, little of this effort is focused on FDS’ conductive heat transfer model, based on the one-dimensional Crank-Nicolson method. Thus, this study aims to test the accuracy of FDS’ conduction model by comparing it to calculations using FEM (Finite Element Method). FDS simulations were created so as to facilitate the study of a wall and its boundary conditions with as little interference from other factors as possible. This to create a controlled environment which easily could be replicated in the subsequent FE-calculations of the conductive heat flow through the solid obstructions. Three different walls (10 cm concrete, 20 cm concrete and 1 mm steel), each with the three different boundary conditions for the rear surface (Exposed, Void and Insulated), were exposed to three different temperatures (100 °C, 500 °C and 1000 °C) for a total of 27 FDS simulations. The adiabatic surface temperature was measured in each simulation in FDS and used as input for the corresponding FE-calculations. The results showed no clear inconsistencies in the boundary conditions, given enough time for thermal penetration they affected the resulting temperatures as expected. Save a slight deviation in the steel walls exposed to 100 °C and 500 °C with boundary conditions Exposed and Void where FDS slightly underestimated the temperature relative to the FE-calculations. The gas temperatures in the grid cells closest to the wall were found to be unreliable as they tended to undergo substantial fluctuations, likely as a result of how FDS handles the discretization of non-solid space for the Navier-Stokes calculations. These fluctuations were however not found to affect the solid temperatures as the mean gas temperature was accurate. FDS was also found to have a tendency to slightly overestimate the surface temperature in the first few minutes of the simulations relative to the FE-calculations. Though the resulting temperatures from the two methods converged after a few minutes at most in all tests. These deviations were considered to have too minor an impact on the solid temperature to justify claims of inaccuracy in FDS. Thus, the general conclusion of this study is that FDS’ predictions of solid phase temperatures are sufficiently accurate within these delimitations.
|
5 |
A Comparative Study on Combustion Behaviours of Polyurethane Foams with Numerical Simulations using Pyrolysis ModelsPau, Dennis Su Wee January 2013 (has links)
This research investigates the decomposition and burning behaviours of polyurethane foams experimentally and compares the experimental results obtained with the numerical results from the pyrolysis model of Fire Dynamics Simulator, Version 5 (FDS 5). Based on the comparison of model and experimental heat release rates, the accuracy of the pyrolysis model is quantified. In total, this research tested seven polyurethane foams consisting of three non-fire retardant (NFR) and four fire
retardant (FR) foams. According to the simultaneous differential scanning calorimetry and thermogravimetric analysis (SDT) experiments, the decomposition behaviour of polyurethane foams under nitrogen environment is represented by two pyrolysis
reactions. The first reaction consists of foam decomposition into melts and gases while the second reaction consists of the decomposition of the remaining melts into gases.
The kinetic properties which govern the rate of decomposition are the activation energy (E), pre-exponential factor (A), reaction order (n) and heat of reaction (Δhr). Using graphical techniques, E, A and n of the first and second reactions are
determined from the thermogravimetric analysis (TGA) results. Through analysing the differential scanning calorimetry (DSC) results, Δhr is determined from the changes in heat flow and sample mass. The thermophysical properties govern the heat
transfer through material and these are the thermal conductivity (λ) and specific heat (cp) which are measured experimentally at ambient temperature through the Hot Disk method.
Through the Sample Feeding Vertical Cone, the decomposition and melting behaviours of polyurethane foams in a vertical orientation are investigated and the foams tested can be categorised into those which produce melts only after ignition and
those which produce melts and char after ignition. The 1-dimensional burning behaviour of foams is obtained from the cone calorimeter experiments. The NFR foams show a change from plateau burning behaviour at low heat flux to two stage burning behaviour at high heat flux while the FR foams consistently show two stage burning behaviour. The combustion property governs the amount of heat released when fuel combusts and this is the effective heat of combustion (Δhc,eff) which is determined from the heat released and mass consumed in the cone experiment.
The 1-dimensional burning behaviour is simulated using the pyrolysis model of FDS 5 and two different modelling approaches are considered. The direct method uses the material properties determined experimentally as FDS 5 inputs while the refined
method uses the genetic algorithm of Gpyro to refine the kinetic properties which are later used as FDS 5 inputs. The heat release rate of the model and experiment are compared through linear regression analysis which quantifies the accuracy of both
methods. The accuracy is defined as the percentage of data points within the boundary of acceptance which is bounded by 25 % of the greatest experimental heat release rate. This assessment method places greater emphasis on the accuracy of developed burning phases and lesser emphasis on the accuracy of initial growth and final decay. The accuracy of the direct method is found to be 56 % while the refined method with
estimated kinetic properties achieves a higher accuracy of 75 %.
The 2-dimensional burning behaviours are investigated in the foam slab experiments for two different slab thicknesses, 120 and 100 mm. The opposed-flow spread of 120 mm slab is more intense and rapid while for the 100 mm slab, the flame spread is less intense and slow. FDS 5 is used to simulate the experimental results but when the material properties either developed experimentally or refined by Gpyro are used as inputs, the model fails to produce flame spread. This is because FDS 5 does not yet
have the features which address the dynamics of foam melting and the reactive nature of the flame. In order to produce flame spread in the model, E of the reactions have been reduced to increase the decomposition rate.
|
6 |
Tvorba manažerského simulátoru pro řízení zásob ve vybrané společnosti / Management flight simulator for inventory management in selected companyProkop, Tomáš January 2010 (has links)
The main goal of this thesis is to create management flight simulator for inventory management in selected company. The proposed management simulator is developed in the context of the taxonomy of decision support systems. It is a model-oriented system based on the models proposed by me and created a user interface. In this particular situation the application is realized on company Dynavix, that is a manufacturer of navigations. After opening theoretic information about models, computer technologies for systems modeling and individual phases of simulation process, there follows a case study. It is trying to find and recommend appropriate solutions of fluctuations in the need for planning the purchase of navigation Dynavix by using a system dynamics approach (developed model and its testing). The recommended solution is verified by testing hypotheses according to a predefined test scenarios.
|
7 |
Modeling the Ventilation of Natural Animal Shelters in Wildland FiresBova, Anthony Scott 30 August 2010 (has links)
No description available.
|
8 |
Entwicklung einer Schnittstelle zur Visualisierung von Brandsimulationen im virtuellen RaumNabrotzky, Toni 22 December 2023 (has links)
Die Digitalisierung im Bauwesen schreitet immer weiter voran und während in diesem
Zusammenhang oftmals das Stichwort Building Information Modeling (BIM) fällt,
entwickeln sich Disziplinen wie das Brandschutzingenieurwesen (BSI) unabhängig weiter.
Das Brandschutzbüro Brandschutz Consult Ingenieurgesellschaft mbH Leipzig (BCL)
verwendet das BSI, um ingenieurtechnische Verfahren heranzuziehen. BCL verfolgt als
Unternehmensphilosophie das Ziel, mit neuen Methoden und Erkenntnissen ständig die
eigenen Prozesse zu optimieren und zu erweitern.
Unter diesem Gesichtspunkt soll in dieser Arbeit in Kooperation mit BCL untersucht
werden, inwieweit sich die Ergebnisse aus einer Brandsimulation, darunter besonders
der Rauch, in einer virtuellen Realität (engl. Virtual Reality (VR)) darstellen und in
bestehende oder potenzielle Anwendungsfälle integrieren lassen. Dazu soll zunächst mit
einer Betrachtung der brandschutztechnischen Grundlagen inklusive des BSIs und einer
Analyse zum Stand des Brandschutzes in BIM begonnen werden. Im nächsten Schritt
sind für die Brandsimulation bestimmte Fragen zu klären, wie z.B. eine entsprechende
Berechnung technisch abläuft und welche Ausgabedaten und -formate eine solche
Simulation bereitstellt.
Zur Darstellung der Simulationsergebnisse in virtuellen Realitäten werden Grafik.Engines benötigt, die VR-Anwendungen ermöglichen. Wichtige Untersuchungsgegenstände sind z.B. die anwendbaren Programmier- und Skriptsprachen, mit deren Einsatz
die Daten eingelesen und visualisiert werden können. Für die gefundenen Grafik-Engines
wird dann recherchiert, ob es bereits bestehende Anwendungen oder Prozesse zur Darstellung von Brandsimulationen gibt. Ist dies der Fall, sollen deren Workflows untersucht
werden, um anschließend ihre grundsätzliche Einsatzfähigkeit zu bewerten und Verbesserungsvorschläge zu äußern...:1. Prozesse im Brandschutz
1.1. Brandschutztechnische Grundlagen
1.2. Angewandte Ingenieurmethoden
1.3. Brandschutz mit Building Information Modeling
2. Ablauf einer Brandsimulation
2.1. Verfügbare Software
2.2. Aufbau einer FDS-Eingabedatei
2.3. Generieren von Simulationsdaten in FDS
2.4. Ausgabedaten und -formate
3. Software zur Darstellung in VR
3.1. Blender
3.2. Unity Engine
3.3. Unreal Engine
3.4. Vergleich der Engines
4. Visualisierung der Brandsimulation
4.1. Konzept der Datenübertragung
4.2. Bestehende Workflows für VR-Programme
4.3. Versuchsdurchführung
4.4. Auswertung der Versuche
5. Anwendungsfälle und Optimierungspotenzial
5.1. Potenzielle Einsatzmöglichkeiten
5.2. Optimierungspotenzial
6. Fazit
A. Beispielmodell Blender
B. Beispielmodell VRSmokeVis
C. Prüfmodell
Abkürzungsverzeichnis
Abbildungsverzeichnis
Tabellenverzeichnis
Literaturverzeichnis / Digitization in the construction industry is progressing and while the keyword Building
Information Modeling (BIM) is frequently mentioned, disciplines like the fire safety
engineering are also evolving independently. The fire protection office Brandschutz Consult Ingenieurgesellschaft mbH Leipzig (BCL)) uses fire safety engineering for including
engineering procedures. As a corporate philosophy BCL pursues the goal of constantly
optimizing and expanding its own processes with new methods and scientific findings.
From this point of view, in cooperation with BCL, this master thesis will examine to
which extent it is possible to visualize the results of a fire simulation, in particular
including the smoke, in Virtual Reality (VR) and to integrate them into existing or
evolving applications. For this purpose, a consideration of the fire protection basics
including fire protection engineering and an analysis of the status of fire protection in
BIM has been started. In the next step the fire simulation must be investigated, i.e. how
the corresponding calculation technically works and which output data and formats
such a simulation provides.
Graphic engines that enable VR applications are required to display the simulation
results in VR. Important objects of investigation are e.g. the applicable programming
and scripting languages. Those scripting languages are used to import and visualize
the data. For the graphic engines found, research is initiated to determine whether
there are already existing applications or processes for displaying fire simulations. If
this is the case these workflows should be examined in order to subsequently evaluate
their fundamental usability and to express suggestions for improvement. If possible,
some of the optimizations should be carried out. Based on the existing processes in fire
protection helpful application options are derived, for which the use must be proven in
future projects.:1. Prozesse im Brandschutz
1.1. Brandschutztechnische Grundlagen
1.2. Angewandte Ingenieurmethoden
1.3. Brandschutz mit Building Information Modeling
2. Ablauf einer Brandsimulation
2.1. Verfügbare Software
2.2. Aufbau einer FDS-Eingabedatei
2.3. Generieren von Simulationsdaten in FDS
2.4. Ausgabedaten und -formate
3. Software zur Darstellung in VR
3.1. Blender
3.2. Unity Engine
3.3. Unreal Engine
3.4. Vergleich der Engines
4. Visualisierung der Brandsimulation
4.1. Konzept der Datenübertragung
4.2. Bestehende Workflows für VR-Programme
4.3. Versuchsdurchführung
4.4. Auswertung der Versuche
5. Anwendungsfälle und Optimierungspotenzial
5.1. Potenzielle Einsatzmöglichkeiten
5.2. Optimierungspotenzial
6. Fazit
A. Beispielmodell Blender
B. Beispielmodell VRSmokeVis
C. Prüfmodell
Abkürzungsverzeichnis
Abbildungsverzeichnis
Tabellenverzeichnis
Literaturverzeichnis
|
9 |
FDS Modelling of Hot Smoke Testing, Cinema and Airport ConcourseWebb, Alex K 06 December 2006 (has links)
"The construction of smoke hazard management systems in large buildings such as shopping malls, cinemas, airports and train stations are increasingly being based on performance based design. Hot smoke tests are a method of using simulated fire conditions to evaluate the functionality of the completed building and the installed systems without causing damage. The author amongst others performed hot smoke tests (HST) according to Australian Standard AS 4391 -1999 in several buildings. In some tests air temperatures, air speed and smoke optical density were recorded at several locations during the test of which two tests are reported. These were later modelled by the author using Fire Dynamic Simulator (FDS) to show that typical fire protection engineering consultant applying the computer model may reasonably predict some results comparable to a full sized simulation scenario. However, some aspects were not well predicted. The modelling was improved by the outcomes of an investigation of the relationship between fuel properties, plume temperature and dynamics, and grid sensitivity. Areas of potential further improvement were identified. This work highlighted that the conditions witnessed in a hot smoke test can provide a guide, but do not represent all aspects of a real fire or design fire scenario. Although the FDS hot smoke model predicted comparable results to the hot smoke test, whilst suitable for system design, computer modelling should never be used as a system installation certification tool. Data from hot smoke tests, if gathered cost effectively, can be a valuable resource for computer model verification."
|
10 |
A Study on Pulsation In Runehamar Tunnel Fire Tests With Forced Longitudinal VentilationKim, Mihyun Esther 05 October 2006 (has links)
"Fire tests involving heavy goods vehicles (HGVs) in a road tunnel with forced ventilation in Norway, conducted by SP, demonstrated a pulsation phenomena that is similar to oscillating flames and thermo-acoustic instabilities previously observed in vitiated compartments and resonant systems that meet the Rayleigh criterion, respectively. This current study investigates whether the causal phenomena can be determined using either a simple, one-dimensional fluid dynamics model or a computation fluid dynamics program. It is assumed that the leading cause for pulsation is a locally under-ventilated fire. Theoretical analysis shows that this assumption is valid and how such conditions can cause the flow field to change. A simple model is developed for a tunnel fire with forced, longitudinal ventilation. The results qualitatively represent the test data and support the assumption of a locally vitiated fire. A more sophisticated analysis, involving the Fire Dynamics Simulator (FDS) Version 4.0, provides similar results. Although FDS calibration, using similar experiment data from the Memorial Tunnel Ventilation Test Program, demonstrates model limitations in predicting smoke layers near the solid boundaries under forced flow field, the qualitative results from both models indicates that pulsation in large tunnel fires under forced ventilation conditions results from poor mixing of the bulk flow in the near field of the fire."
|
Page generated in 0.0588 seconds