1 |
Distance Protection Aspects of Transmission Lines Equipped with Series Compensation CapacitorsSummers, Clinton Thomas 22 October 1999 (has links)
In order to meet the high demand for power transmission capacity, some power companies have installed series capacitors on power transmission lines. This allows the impedance of the line to be lowered, thus yielding increased transmission capability. The series capacitor makes sense because it's simple and could be installed for 15 to 30% of the cost of installing a new line, and it can provide the benefits of increased system stability, reduced system losses, and better voltage regulation.1
Protective distance relays, which make use of impedance measurements in order to determine the presence and location of faults, are "fooled" by installed series capacitance on the line when the presence or absence of the capacitor in the fault circuit is not known a priori. This is because the capacitance cancels or compensates some of the inductance of the line and therefore the relay may perceive a fault to be in its first zone when the fault is actually in the second or third zone of protection. Similarly, first zone faults can be perceived to be reverse faults! Clearly this can cause some costly operating errors.
The general approach of interest is a method leading to the determination of the values of series L and C of the line at the time of the fault. This is done by analyzing the synchronous and subsynchronous content of the V and I signals seperately which provides adequate information to compute the series L and C of the line. / Master of Science
|
2 |
Control of Dynamically Assisted Phase-shifting TransformersJohansson, Nicklas January 2008 (has links)
<p>In this thesis, controllers for power oscillation damping, transient stability improvement and power flow control by means of a Controlled Series Compensator (CSC) and and a Dynamic Power Flow Controller (DPFC) are proposed. These devices belong to the group of power system components referred to as Flexible AC Transmission System (FACTS) devices. The developed controllers use only quantities measured locally at the FACTS device as inputs, thereby avoiding the risk of interrupted communications associated with the use of remote signals for control.</p><p>For power systems with one dominating, poorly damped inter-area power oscillation mode, it is shown that a simple generic system model can be used as a basis for damping- and power flow control design. The model for control of CSC includes two synchronous machine models representing the two grid areas participating in the oscillation and three reactance variables, representing the interconnecting transmission lines and the FACTS device. The model for control of DPFC is of the same type but it also includes the phase shift of the internal phase-shifting transformer of the DPFC.</p><p>The key parameters of the generic grid models are adaptively set during the controller operation by estimation from the step responses in the FACTS line power to the changes in the line series reactance inserted by the FACTS device. The power oscillation damping controller is based on a time-discrete, non-linear approach which aims to damp the power oscillations and set the desired power flow on the FACTS line by means of two step changes in the line reactance separated in time by half an oscillation cycle.</p><p>A verification of the proposed controllers was done by means of digital simulations using power system models of different complexities. The CSC and DPFC controllers were shown to significantly improve the small-signal- and transient stability in one four-machine system of a type commonly used to study inter-area oscillations. The CSC controller was also tested for 18 different contingencies in a 23-machine system, resulting in an improvement in both the system transient stability and the damping of the critical oscillation mode. </p>
|
3 |
Control of Dynamically Assisted Phase-shifting TransformersJohansson, Nicklas January 2008 (has links)
In this thesis, controllers for power oscillation damping, transient stability improvement and power flow control by means of a Controlled Series Compensator (CSC) and and a Dynamic Power Flow Controller (DPFC) are proposed. These devices belong to the group of power system components referred to as Flexible AC Transmission System (FACTS) devices. The developed controllers use only quantities measured locally at the FACTS device as inputs, thereby avoiding the risk of interrupted communications associated with the use of remote signals for control. For power systems with one dominating, poorly damped inter-area power oscillation mode, it is shown that a simple generic system model can be used as a basis for damping- and power flow control design. The model for control of CSC includes two synchronous machine models representing the two grid areas participating in the oscillation and three reactance variables, representing the interconnecting transmission lines and the FACTS device. The model for control of DPFC is of the same type but it also includes the phase shift of the internal phase-shifting transformer of the DPFC. The key parameters of the generic grid models are adaptively set during the controller operation by estimation from the step responses in the FACTS line power to the changes in the line series reactance inserted by the FACTS device. The power oscillation damping controller is based on a time-discrete, non-linear approach which aims to damp the power oscillations and set the desired power flow on the FACTS line by means of two step changes in the line reactance separated in time by half an oscillation cycle. A verification of the proposed controllers was done by means of digital simulations using power system models of different complexities. The CSC and DPFC controllers were shown to significantly improve the small-signal- and transient stability in one four-machine system of a type commonly used to study inter-area oscillations. The CSC controller was also tested for 18 different contingencies in a 23-machine system, resulting in an improvement in both the system transient stability and the damping of the critical oscillation mode. / QC 20101112
|
4 |
Determination of Single Pole Breaker Reclose Time and System Performance Using Real Time SimulationGodavarthi, Venkata Sridivya 19 May 2017 (has links)
This thesis investigates single pole reclosing in series capacitor compensated line. An algorithm is developed to determine the optimal dead time required for single pole reclose of circuit breakers and to reduce the randomness of reclosing time. The algorithm considers conditions of system, fault, voltage zero crossing, arc, and IEEE C37.104-2012 standard de-ionization time. This study also addresses difficulties of single pole reclose operation such as over-voltages at the line, secondary arc extinguishing time, dead time, over-voltages across the series capacitor, and negative sequence current. The system performance is evaluated using a set of metrics based on those operation difficulties. Methods used in the industry such as shunt reactor with the neutral reactor, surge arrester, and MOV are modelled and simulated to capture their effect on the operation difficulties. Comparative analysis is made to rank the effectiveness of each element against difficulties in operating single pole reclosing of circuit breakers.
|
5 |
Synchronous Voltage Reversal Control of Thyristor Controlled Series CapacitorÄngquist, Lennart January 2002 (has links)
Series compensation of transmission lines is an effectiveand cheap method of improving the power transmission systemperformance. Series capacitors virtually reduces the length ofthe line making it easier to keep all parts of the power systemrunning in synchronism and to maintain a constant voltage levelthroughout the system. In Sweden this technology has been inuse since almost 50 years. The possibility to improve the performance of the ACtransmission system utilizing power electronic equipment hasbeen discussed a lot since about ten years. Some newsemiconductor based concepts have been developed beside thesince long established HVDC and SVC technologies. The ThyristorControlled Series Capacitor (TCSC) is one such concept. Byvarying the inserted reactance an immediate and well-definedimpact on the active power flow in the transmission line isobtained. Several potential applications, specifically poweroscillation damping, benefit from this capability. The conceptimplied the requirement to design a semiconductor valve, whichcan be inserted directly in the high-voltage power circuit.This certainly presented a technical challenge but thestraightforward approach appeared to be a cost-effectivealternative with small losses. It was also realized that the TCSC exhibits quite differentbehaviour with respect to subsynchronous frequency componentsin the line current as compared to the fixed series capacitorbank. This was a very interesting aspect as the risk ofsubsynchronous resonance (SSR), which just involves such linecurrent components, has hampered the use of series compensationin power systems using thermal generating plants. The thesis deals with the modelling and control aspects ofTCSC. A simplifying concept, the equivalent, instantaneousvoltage reversal, is introduced to represent the action of thethyristor controlled inductive branch, which is connected inparallel with the series capacitor bank in the TCSC. The idealvoltage reversal is used in the thesis in order to describe andexplain the TCSC dynamics, to investigate its apparentimpedance at various frequencies, as a platform forsynthesizing the boost control system and as the base elementin deriving a linear, small-signal dynamical model of thethree-phase TCSC. Quantitative Feedback Theory (QFT) then hasbeen applied to the TCSC model in order to tune its boostregulator taking into account the typical variation ofparameters that exists in a power system. The impact of theboost control system with respect to damping of SSR is finallybeing briefly looked at. <b>Keywords:</b>Thyristor Controlled Series Capacitor, TCSC,FACTS, reactive power compensation, boost control, phasorestimation, Quantitative Feedback Theory, subsynchronousresonance, SSR.
|
6 |
Synchronous Voltage Reversal Control of Thyristor Controlled Series CapacitorÄngquist, Lennart January 2002 (has links)
<p>Series compensation of transmission lines is an effectiveand cheap method of improving the power transmission systemperformance. Series capacitors virtually reduces the length ofthe line making it easier to keep all parts of the power systemrunning in synchronism and to maintain a constant voltage levelthroughout the system. In Sweden this technology has been inuse since almost 50 years.</p><p>The possibility to improve the performance of the ACtransmission system utilizing power electronic equipment hasbeen discussed a lot since about ten years. Some newsemiconductor based concepts have been developed beside thesince long established HVDC and SVC technologies. The ThyristorControlled Series Capacitor (TCSC) is one such concept. Byvarying the inserted reactance an immediate and well-definedimpact on the active power flow in the transmission line isobtained. Several potential applications, specifically poweroscillation damping, benefit from this capability. The conceptimplied the requirement to design a semiconductor valve, whichcan be inserted directly in the high-voltage power circuit.This certainly presented a technical challenge but thestraightforward approach appeared to be a cost-effectivealternative with small losses.</p><p>It was also realized that the TCSC exhibits quite differentbehaviour with respect to subsynchronous frequency componentsin the line current as compared to the fixed series capacitorbank. This was a very interesting aspect as the risk ofsubsynchronous resonance (SSR), which just involves such linecurrent components, has hampered the use of series compensationin power systems using thermal generating plants.</p><p>The thesis deals with the modelling and control aspects ofTCSC. A simplifying concept, the equivalent, instantaneousvoltage reversal, is introduced to represent the action of thethyristor controlled inductive branch, which is connected inparallel with the series capacitor bank in the TCSC. The idealvoltage reversal is used in the thesis in order to describe andexplain the TCSC dynamics, to investigate its apparentimpedance at various frequencies, as a platform forsynthesizing the boost control system and as the base elementin deriving a linear, small-signal dynamical model of thethree-phase TCSC. Quantitative Feedback Theory (QFT) then hasbeen applied to the TCSC model in order to tune its boostregulator taking into account the typical variation ofparameters that exists in a power system. The impact of theboost control system with respect to damping of SSR is finallybeing briefly looked at.</p><p><b>Keywords:</b>Thyristor Controlled Series Capacitor, TCSC,FACTS, reactive power compensation, boost control, phasorestimation, Quantitative Feedback Theory, subsynchronousresonance, SSR.</p>
|
7 |
Vývoj a ověření DC/DC měniče pro budoucí automobilové osvětlovací systémy s palubním napětím 48V / Development and Verification of DC/DC Converter for Future Automotive Lighting Systems with Net Voltage of 48VPospíšil, Josef January 2018 (has links)
The aim of this master thesis is to describe the requirements put on electronics and headlights within car industry, above all on the newly emerging 48V power network. In the thesis the principles of chosen DC/DC buck converter topologies are briefly described. In the next part of this thesis the converters are designed and manufactured. Further, the EMC chamber measurement of these converters and their subsequent evaluation is performed. In the last part the proposed converters are compared and evaluated.
|
8 |
Supervisory control scheme for FACTS and HVDC based damping of inter-area power oscillations in hybrid AC-DC power systemsHadjikypris, Melios January 2016 (has links)
Modern interconnected power systems are becoming highly complex and sophisticated, while increasing energy penetrations through congested inter-tie lines causing the operating point approaching stability margins. This as a result, exposes the overall system to potential low frequency power oscillation phenomena following disturbances. This in turn can lead to cascading events and blackouts. Recent approaches to counteract this phenomenon are based on utilization of wide area monitoring systems (WAMS) and power electronics based devices, such as flexible AC transmission systems (FACTS) and HVDC links for advanced power oscillation damping provision. The rise of hybrid AC-DC power systems is therefore sought as a viable solution in overcoming this challenge and securing wide-area stability. If multiple FACTS devices and HVDC links are integrated in a scheme with no supervising control actions considered amongst them, the overall system response might not be optimal. Each device might attempt to individually damp power oscillations ignoring the control status of the rest. This introduces an increasing chance of destabilizing interactions taking place between them, leading to under-utilized performance, increased costs and system wide-area stability deterioration. This research investigates the development of a novel supervisory control scheme that optimally coordinates a parallel operation of multiple FACTS devices and an HVDC link distributed across a power system. The control system is based on Linear Quadratic Gaussian (LQG) modern optimal control theory. The proposed new control scheme provides coordinating control signals to WAMS based FACTS devices and HVDC link, to optimally and coherently counteract inter-area modes of low frequency power oscillations inherent in the system. The thesis makes a thorough review of the existing and well-established improved stability practises a power system benefits from through the implementation of a single FACTS device or HVDC link, and compares the case –and hence raises the issue–when all active components are integrated simultaneously and uncoordinatedly. System identification approaches are also in the core of this research, serving as means of reaching a linear state space model representative of the non-linear power system, which is a pre-requisite for LQG control design methodology.
|
9 |
Theoretical Analysis and Design for the Series-Resonator Buck ConverterTu, Cong 03 February 2023 (has links)
High step-down dc/dc converters are widely adopted in a variety of areas such as industrial, automotive, and telecommunication. The 48 V power delivery system becomes increasingly popular for powering high-current and low-voltage chips. The Series-Capacitor Buck (SCB) converter doubles the duty ratio and equalizes the current between the two phases. Hard switching has hindered efforts to reduce volume via increased switching frequency, although a monolithically integrated SCB converter has boosted current density. A Series-Resonator Buck (SRB) converter is realized by adding a resonant tank in series with the series capacitor Cs. All switches turn on at zero-voltage (ZVOn), and the low-side switches turn off at zero-current (ZCOff). The design of the SRB converter includes characterizing the design variables' impacts on the converter performances and designing low-loss resonant components as the series resonator.
The Series-Resonator Buck converter belongs to the class of quasi-resonant converters. Its resonant frequency is higher than the switching frequency, and its waveforms are quasi-sinusoidal. This work develops a steady-state model of the SRB converter to calculate voltage gain, component peak voltages, and resonant inductor peak current. Each switching cycle is modeled based on the concept of generalized state-space averaging. The soft-switching condition of the high-side switches is derived. The ZVS condition depends on the normalized control variable and the load condition. The gain equation models the load-dependent characteristic and the peak gain boundary. The theoretical peak voltage gain of the SRB converter is smaller than the maximum gain of the SCB converter. A smaller normalized load condition results in a larger peak voltage gain of the SRB converter.
The large-signal model of the SRB converter characterizes the low-frequency behavior of the low-pass filters with the series capacitor and the high-frequency behavior of the resonant elements. A design recommendation of t_off f_r<0.5 is suggested to avoid the oscillation between the series capacitor Cs and the output inductors Lo. In other words, the off-duration of the low-side switches is less than half of 1/fr, and therefore the negative damping effect from the parallel resonant tank to the vCs response is reduced. The transfer functions of the SRB converter are presented and compared with those of the SCB converter. The series resonator brings in an extra damping effect to the response of output capacitor voltage.
The understanding of the analytical relationships among the resonant tank energy, voltage gain, and component stresses was utilized to guide the converter design of the converter's parameters. A normalized load condition at √2 minimizes the stresses of the series resonator by balancing the peak energy in the resonant elements Lr and Cr. The f_s variation with voltage gain M is less than 10%. The non-resonant components C_s, L_oa, and L_ob are designed according to the specified switching ripples.
The ac winding loss complicates the winding design of a resonant inductor. This work replaces the rectangular window with a rhombic window to reduce the eddy current loss caused by the fringing effect. The window ratio k_y is added as a design variable. The impacts of the design variables on the inductance, core loss, and winding loss are discussed. The air-gap length l_g is designed to control the inductance. A larger k_y design results in a short inductor length l_c and a smaller winding loss. The disadvantages include a smaller energy density design and a larger core loss due to the smaller cross-sectional area. In the design example presented in the thesis, the presence of the rhombic shape increases the gap-to-winding distance by two times, and also reduces the y-component of the magnetic field by a factor of two. The total inductor loss is reduced by 56% compared to a conventional design with a rectangular winding window while keeping the same inductance and the same inductor volume.
This dissertation implements a resonator, replacing the series capacitor, in an SCB converter. The resultant SRB converter shows a 30% reduction in loss and a 50% increase in power density. The root cause of the divergence issue is identified by modeling the negative damping effect caused by resonant elements. The presented transient design guideline clears the barriers to closed-loop regulation and commercialization of the SRB converter. This work also reshapes winding windows from rectangle to rhombus which is a low-cost change that reduces magnetic loss by half. The theoretical analysis and design procedures are demonstrated in a 200 W prototype with 7% peak efficiency increase compared to the commonly used 30 W commercial SCB product. / Doctor of Philosophy / High step-down dc/dc converters are widely adopted in a variety of areas such as industrial, automotive, and telecommunication areas. The 48 V power delivery system becomes increasingly popular for powering high-current and low-voltage chips. The Series-Capacitor Buck (SCB) converter doubles the duty ratio and equalizes the current between the two phases. Hard switching has hindered efforts to reduce volume via increased switching frequency although a monolithically integrated SCB converter has boosted current density. A Series-Resonator Buck (SRB) converter is realized by adding a resonant tank in series with the series capacitor Cs. All switches turn on at zero-voltage (ZVOn), and the low-side switches turn off at zero-current (ZCOff). The challenges to designing the SRB converter include characterizing the design variables' impacts on the converter performances and designing low-loss resonant components as the series resonator.
The resultant SRB converter shows a 30% reduction in loss and a 50% increase in power density. The root cause of the divergence issue is identified by modeling the negative damping effect caused by the resonant elements. The presented transient design guideline clears the barriers of closed-loop regulation and commercialization of the SRB converter. This work also reshapes winding windows from rectangle to rhombus, which is a low-cost change that reduces magnetic loss by half. The theoretical analysis and design procedures are demonstrated in a 200 W prototype with 7% peak efficiency increase compared to the commonly used 30 W commercial SCB product.
|
10 |
Control of transmission system power flowsKreikebaum, Frank Karl 13 January 2014 (has links)
Power flow (PF) control can increase the utilization of the transmission system and connect lower cost generation with load. While PF controllers have demonstrated the ability to realize dynamic PF control for more than 25 years, PF control has been sparsely implemented.
This research re-examines PF control in light of the recent development of fractionally-rated PF controllers and the incremental power flow (IPF) control concept. IPF control is the transfer of an incremental quantity of power from a specified source bus to specified destination bus along a specified path without influencing power flows on circuits outside of the path.
The objectives of the research are to develop power system operation and planning methods compatible with IPF control, test the technical viability of IPF control, develop transmission planning frameworks leveraging PF and IPF control, develop power system operation and planning tools compatible with PF control, and quantify the impacts of PF and IPF control on multi-decade transmission planning.
The results suggest that planning and operation of the power system are feasible with PF controllers and may lead to cost savings. The proposed planning frameworks may incent transmission investment and be compatible with the existing transmission planning process. If the results of the planning tool demonstration scale to the national level, the annual savings in electricity expenditures would be $13 billion per year (2010$). The proposed incremental packetized energy concept may facilitate a reduction in the environmental impact of energy consumption and lead to additional cost savings.
|